2-Energy Management - Lighting, Cable choice

Usual values

NotePower output per phase of a lighting circuit:

  • common values: 0.3 to 0.8 kW;

  • maximum values:

    • 110 V: up to 1 kW,

    • 220 to 240 V: up to 2.2 kW.

NotePower factor:

  • > 0.92 (compensated circuit or electronic ballast).

NoteMaximum admissible voltage drop (>U) in steady state:

  • 3% for circuits less than 100 m;

  • 3.5% permissible above 200 m.

NoteCable cross-section:

  • most commonly (< 20 m): 1.5 or 2.5 mm2;

  • very long (> 50 m) high-power circuit, to limit voltage drops: 4 to 6 mm², or even 10 mm² (> 100 m).