Earthing system TN and IT, design

Simplified method 1: Resistive loop

This method consists on the calculation of the resistance of the wire and checking the length of the cable is below the maximum length given by the formula: {

and

  • : Maximum length of the feeder

  • : Single phase voltage

  • : Contact voltage

  • : Cross section of the live

  • : cross sectionof the earth wire

  • ρ = the resistivity constant of the conductor material at the normal operating temperature being: ( 22.5 mΩ.mm2/m for copper, 36 mΩ.mm2/m for aluminium

  • : rated current of the circuit breaker

To take in account the transformer, the voltage supplying the loop is taken as 80% of the rated value.

Note

We consider that the protection of people is granted if the length of the feeder is less than calculated

Example

A resistive load with a current rating of 9A is supply by a 100m, 3 core, 1,5 sqm copper cable. The protection is ensure by a MCB 10A type C. The maximum contact voltage is

With so

MCB is Type C so So

The Contact voltage is

The contact voltage is dangerous (88V>50V) The maximum length must be 58,6m or the feeder of the load is 100m. THE PROTECTION OF THE PEOPLE IS NOT ENSURED!

To ensure the protection of the people in this situation, in case of insulation fault in the equipment, we must change the characteristics of the circuit:

Change the size of the wires (Costly)

Change the type of MCB (Type B)

Use RCD (Only in TNS!)

PreviousPreviousNextNext
HomepageHomepagePrintPrintCreated with Scenari (new window)